Traditional condition assessment techniques, including Dissolved Gas Analysis for oil-immersed units alongside high-frequency electrical diagnostics such as Frequency Response Analysis, Sweep Frequency Response Analysis, and mechanical vibration monitoring, require substantial operational investments, specialized diagnostic instrumentation, and expert interpretation to yield actionable insights. In response to these operational constraints, diagnostic methodologies utilizing voltage-current diagrams, designated as the delta V-I technique, have emerged as a promising alternative capable of detecting both mechanical distortions and electrical winding failures.
To overcome the operational dependencies and classification errors of manual assessments, researchers modeled a physical 14-kilovolt-ampere dry-type power transformer and formulated an integrated diagnostic pipeline that automates fault identification using machine learning algorithms. Historical failure records indicate that internal winding short circuits alone account for approximately seventy percent of total transformer failures. The newly evaluated structured pipeline couples equivalent high-voltage circuit modeling with automated feature extraction and an adaptive Bayesian model selector, designed specifically to address the detrimental impact of environmental noise and nonlinear electrical disturbances that have historically compromised the reliability of automated voltage-current diagnostic models under real-world industrial substation conditions.
The experimental foundation of the study is centered on the precise geometrical and electrical specification of the high-voltage winding of a 14-kilovolt-ampere dry-type transformer. The high-voltage winding features a layer-type structural geometry composed of four distinct layers with sixteen turns per layer, yielding sixty-four total turns constructed from copper conductor wire measuring one centimeter in height and three millimeters in width. Because each individual conductor turn represents approximately 1.5 percent of the total winding, any localized turn failure significantly alters electrical properties. Geometrical measurements indicate that the turns expand progressively across successive layers, with the inner radius measuring 7.57 centimeters, the external high-voltage radius reaching 9.07 centimeters, and the low-voltage outer radius measuring 6.57 centimeters. Consequently, the conductor turn lengths increase from 47.54 centimeters on the innermost layer to 55.07 centimeters on the outermost layer, establishing an overall winding conductor length of 3283.6 centimeters with a mean turn length of 51.3 centimeters.
To capture the internal electromagnetic behaviors necessary for incipient fault detection, the researchers represented the transformer winding as an equivalent resistance-inductance-capacitance lumped parameter ladder network. Because power frequency operating wavelengths at fifty hertz approximate 3000 kilometers when assuming an electromagnetic propagation velocity of 1.5 times ten to the eighth meters per second, the physical conductor length of roughly thirty-three meters is negligible in comparison to the wavelength, rigorously justifying a lumped parameter formulation over a distributed transmission line representation. Furthermore, analytical justification verified that coupling approximation errors caused by neglecting non-adjacent mutual inductances remain mathematically negligible at power frequencies, where angular velocity approximates 314 radians per second. In the circuit formulation, shunt conductance was omitted to focus the study on turn-to-turn short circuits, buckling stress, and axial displacement rather than leakage faults, while mutual inductances were lumped into series inductances across discrete network elements.
Simulations of the resulting electrical Netlist were performed within a Python Jupyter Notebook environment utilizing the PySpice circuit simulation module under stabilized ambient operating conditions of 25 degrees Celsius, a 220-volt fifty-hertz power source, and a 0.9 power factor. To account for structural variations, non-uniform resistance and series inductance parameters were vectorially mapped across the four winding layers, reflecting conductor length variations. Mathematical modeling of voltage distribution across the winding demonstrated that the steady-state electrical potential is uniformly distributed along the entire conductor length at power frequencies, allowing the electrical signatures of localized turn defects to be systematically extracted. Simulated fault mechanisms were introduced into the circuit model: turn-to-turn faults by short-circuiting specific winding elements, axial displacement by modifying self and mutual inductances to replicate magnetic imbalance, and buckling stress by reducing series capacitance and mutual inductance by ten percent while increasing shunt capacitances by ten percent.
The dynamic evolution of the simulated voltage-current diagrams was quantitatively tracked using three primary dimensionless geometric ratios: the ratio of faulty diagram area to healthy diagram area, the ratio of faulty perimeter to healthy perimeter, and the ratio of faulty diagram angle to healthy diagram angle. Recording these diagnostic indicators across independent fault injections across all four winding layers generated an initial baseline dataset of 588 samples, structured as 196 instances across three diagnostic features. Initial correlation analysis indicated that these fundamental geometric features were highly correlated, which can distort classification boundaries. To project higher-order non-linear boundary dynamics, the researchers generated four engineered mathematical features: the numerical difference between the angle and perimeter ratios, their direct quotient, the quotient of the perimeter to area ratios, and the squared Euclidean sum of all three primary ratios, creating an expanded dataset of 1372 samples.
Feature space transformations were subsequently analyzed using both Principal Component Analysis and Linear Discriminant Analysis to evaluate class separability. In the unsupervised Principal Component Analysis projection, the three fault classes formed overlapping parabolic trajectories, where buckling stress and axial displacement converged at identical points and turn-to-turn short circuits overlapped significantly with axial displacement. Conversely, the supervised Linear Discriminant Analysis projection significantly expanded inter-class variance, establishing distinct spatial separation between class centers. An ablation study confirmed that the four newly engineered mathematical features enabled the Linear Discriminant Analysis framework to capture higher-order discriminatory boundaries that the raw geometric ratios could not provide. The physical overlap between fault signatures stems from the reality that axial displacement and buckling stresses concurrently modify winding capacitances and inductances, generating similar spectral signatures at discrete operating frequencies.
To prevent data leakage—a pervasive vulnerability in machine learning evaluations with small sample sizes—the entire classification workflow was encapsulated within an automated machine learning pipeline combining standard scaling normalization, Linear Discriminant Analysis dimensionality reduction, and classification. Hyperparameter optimization was conducted via exhaustive grid search across discrete Cartesian parameter sets, targeting the global optimum based on cross-validated accuracy. Model performance was statistically evaluated across nine distinct algorithms using stratified five-fold cross-validation, ensuring identical fault class distributions across every fold while computing scaling and projection parameters exclusively from fold-specific training subsets. The candidate algorithms comprised AdaBoost.M2, Random Forest, Extra Trees, Gradient Boosting, XGBoost, LightGBM, Support Vector Machines, Logistic Regression, and k-Nearest Neighbors.
In baseline comparative evaluations under clean signal conditions, the Support Vector Machine classifier achieved the highest diagnostic performance, attaining an overall classification accuracy of 89 percent, a mean cross-validated accuracy of 87 percent, and a Cohen’s kappa coefficient of 83 percent. Across individual fault categories, the Support Vector Machine yielded a precision of 100 percent for turn-to-turn short circuits, 78 percent for axial displacement, and 90 percent for buckling stress. Random Forest, Extra Trees, and Logistic Regression achieved 87 percent accuracy, whereas Gradient Boosting and k-Nearest Neighbors recorded 82 percent, and XGBoost achieved 80 percent. Pairwise McNemar chi-squared tests with Edwards continuity correction demonstrated statistical equivalence among ensemble tree models, such as Random Forest and XGBoost with a p-value of 1.0, while identifying significant structural divergence between Support Vector Machines and k-Nearest Neighbors at a p-value of 0.0004.
To systematically evaluate operational resilience against real-world substation interference, researchers simulated Additive White Gaussian Noise across signal-to-noise ratios ranging from five decibels up to eighty decibels. The injection of noise demonstrated that diagnostic accuracy degrades across all nine algorithms, yet individual models exhibited starkly different performance profiles depending on noise severity. Under severe noise conditions at 5 decibels, classifier accuracies ranged from 57 percent for XGBoost to 69 percent for the Support Vector Machine. At 80 decibels, ensemble tree models achieved peak performance of 83 percent. Between 20 and 80 decibels, Random Forest, Extra Trees, and k-Nearest Neighbors demonstrated sustained diagnostic accuracy, whereas the Support Vector Machine and Logistic Regression maintained stable classification boundaries across all regimes exceeding 20 decibels. Receiver operating characteristic curves for the Support Vector Machine at 20 decibels produced area-under-the-curve values ranging from 0.83 to 0.96 across folds.
Because practical substation monitoring systems face dynamic, non-stationary noise environments where true signal-to-noise ratios cannot be known in advance, the authors developed an adaptive Bayesian model selector. Operational noise is continuously estimated from live time-series data using Donoho’s wavelet estimator, which calculates the noise variance from the Median Absolute Deviation of the finest detail coefficients of a sliding discrete wavelet transform. The signal power is then determined by subtracting estimated noise variance from total signal variance. The resulting noise estimate feeds an adaptive Bayesian inference engine that continuously updates posterior probabilities by combining training priors with incoming observations, selecting the optimal algorithm via a maximum a posteriori argmax operator. This probabilistic selection prevents erratic algorithm switching at threshold boundaries and enables the dynamic diagnostic system to consistently match or exceed the performance of the strongest individual classifier across all operational noise levels.
Notwithstanding the high diagnostic accuracy demonstrated by the adaptive Bayesian pipeline, the authors noted several critical technical constraints inherent to the current investigation. Foremost, the evaluation relies entirely on computational circuit simulations of a 14-kilovolt-ampere transformer rather than empirical laboratory measurements on energized hardware. Furthermore, simplifying the magnetic circuit by lumping mutual inductances into series inductances necessarily omitted fine-grained magnetic coupling signatures unique to mechanical deformations, contributing to the persistent boundary overlaps observed between axial displacement and buckling stresses. Consequently, future research must implement comprehensive dynamic mutual inductance matrices to enhance diagnostic sensitivity, validate the framework across physical experimental testbeds, and expand the underlying machine learning models to identify a broader taxonomy of transformer fault mechanisms.
Subject of Research: Machine learning and voltage-current technique for power transformer fault diagnosis
Article Title: A structured pipeline with an adaptive Bayesian model selector for power transformer fault diagnosis using machine learning and voltage-current technique
Article References: Ngong, S. M., Maxime, F. S., Gonza, M., Guy-de-patience, F. M., & Ngasop, N. (2026). A structured pipeline with an adaptive Bayesian model selector for power transformer fault diagnosis using machine learning and voltage-current technique. Measurement: Energy, 11, Article 100112. https://doi.org/10.1016/j.meaene.2026.100112
Image Credits: AI Generated
DOI: 10.1016/j.meaene.2026.100112
Keywords: Power Transformers, Fault Diagnosis, Voltage-Current Diagram, Machine Learning, Support Vector Machine, Bayesian Inference, Lumped Parameter Ladder Network, Linear Discriminant Analysis, Principal Component Analysis, Wavelet Noise Estimation, Additive White Gaussian Noise, Turn-to-Turn Short Circuit, Axial Displacement, Buckling Stress, Stratified K-Fold Cross-Validation, Donoho Estimator
News Source: Ophelia Keating. (November 25, 2026). Adaptive Bayesian Model Selector Optimizes Power Transformer Fault Diagnosis Under Variable Noise. Scienmag.