A two-stage coordinated dispatch framework that links dynamic carbon emission responsibility with vehicle-to-grid interaction reduced total operating costs by 3.87 percent, trimmed carbon emissions by 13.78 percent, and narrowed the peak-to-valley load difference by 58.50 percent compared with a conventional price-guided benchmark in a simulated regional power system. The modeling investigation, published in the Journal of Engineering and Applied Science by Tingjie Ba, Hongyi Zeng, Wanjun Wu, Dong Jiao, and Yongyuan Huang, evaluates how modern power networks can balance supply, transmission, demand, and storage under the operational uncertainties introduced by rising shares of variable renewable generation. Traditional source–grid–load–storage scheduling relies heavily on time-of-use electricity prices, an economic incentive structure that fails to reflect temporal fluctuations in carbon intensity and overlooks the operational flexibility of distributed energy assets.
The physical architecture evaluated in the study couples localized generation, grid exchanges, and flexible end-user resources across a simulated 24-hour horizon divided into one-hour scheduling intervals. On the supply side, the regional network incorporates distributed photovoltaic arrays and biomass combustion units as renewable sources, alongside a controllable natural gas-fired micro gas turbine that provides dispatchable power. These local generators interact bidirectionally with the upstream external grid, purchasing power during generation deficits and exporting clean electricity during periods of surplus production. On the demand side, baseline consumer electricity consumption is paired with controllable flexible loads, stationary electrochemical energy storage systems, and aggregated clusters of electric vehicles equipped with vehicle-to-grid bidirectional charging technology.
To overcome the carbon-blind nature of standard time-of-use pricing, the researchers formulated a dynamic carbon emission responsibility factor, denoted as Cr(t), which quantifies the carbon responsibility assigned per unit of electricity consumed across the network at any given hour. This factor calculates the weighted emission profile of all operational power supply units, accounting for the load factors of conventional generation sources. Upstream grid imports are modeled on conventional thermal generation, while local micro gas turbine outputs follow gas-fired performance curves. Photovoltaic and biomass units operate with negligible direct combustion emissions, meaning their operational carbon coefficient mirrors the prevailing system-level factor. Stationary energy storage inherits and tracks the carbon intensity of the specific electricity absorbed during preceding charging intervals, ensuring historical emission values carry forward into subsequent discharge periods.
Electric vehicles serve as mobile, decentralized energy storage units whose aggregated flexibility depends on the stochastic travel behaviors of private vehicle owners. The researchers characterized fleet behavioral patterns through Monte Carlo sampling grounded in travel statistics from the United States Department of Transportation, using normal distribution probability density functions to model plug-in arrival times, departure times, and initial battery states of charge. Connected vehicles were partitioned into operational subgroups to simplify computational optimization while preserving operational diversity. Fleet-level constraints strictly enforce bidirectional power limits, charge and discharge conversion efficiencies, and cumulative energy boundaries to guarantee that each vehicle retains sufficient energy to meet its target state of charge upon departure, alongside an equivalent linear degradation cost model that captures battery wear caused by repeated cycling.
Environmental policy mechanisms were integrated into the economic modeling layer to monetize clean energy operations through a coupled market structure comprising carbon emission trading, green certificate trading, and China Certified Emission Reduction credits. Free carbon allowances cover both indirect emissions from grid purchases and direct emissions from micro gas turbine combustion, penalizing net emissions exceeding benchmark allocations. To reward carbon displacement, a virtual green electricity accounting system tracks solar power captured by stationary storage and subsequently discharged during peak periods to displace fossil-fuel generation, credited at an emission reduction rate of 0.5 metric tons of carbon dioxide per megawatt-hour. Additionally, surplus photovoltaic generation exported directly to the main transmission network qualifies for environmental revenue through tradable green certificates.
The dispatch procedure is resolved across two successive stages: pre-dispatch and re-dispatch. In the pre-dispatch phase, electric vehicles are treated as rigid, non-flexible charging loads, and the system minimizes comprehensive operating expenditures—including fuel use, equipment maintenance, demand response compensations, and net grid purchases—to determine baseline unit commitment schedules and calculate the time-varying carbon emission responsibility factor. In the subsequent re-dispatch phase, this carbon factor acts as a dynamic operational guidance signal alongside time-of-use prices. The re-dispatch model incorporates trapezoidal fuzzy chance constraints based on credibility theory to accommodate photovoltaic generation forecasting uncertainties, coordinating electric vehicles, stationary storage, and responsive loads under a multi-objective framework that simultaneously targets cost minimization and load-profile smoothing through a normalized weighted-sum formulation.
Numerical simulations conducted on a regional power network model configured in MATLAB R2025b with YALMIP and solved using Gurobi Optimizer 12.0.3 revealed sharp divergences between price signals and environmental metrics. In the pre-dispatch analysis, early morning hours between 00:00 and 10:00 exhibited low electricity prices but elevated carbon responsibility factors, driven by heavy reliance on carbon-intensive upstream grid imports to meet base demand and initial charging requirements. Between 10:00 and 18:00, surging solar irradiance caused photovoltaic output to dominate the energy supply, driving the carbon emission responsibility factor down sharply as zero-carbon generation supplied local loads, charged storage units, and exported excess clean electricity to the upstream grid. Evening hours between 19:00 and 24:00 saw solar generation drop to zero, prompting the dispatch of biomass, storage, and gas turbines to curb external purchases.
To evaluate individual and combined operational mechanisms, the authors analyzed four distinct re-dispatch scenarios. In Scenario 1, functioning as the benchmark, dispatch was guided solely by time-of-use pricing without vehicle-to-grid support, resulting in total operating costs of 12,092.21 Chinese yuan, carbon emissions of 12.70 metric tons, and a peak-to-valley load spread of 626.81 kilowatts. Scenario 2 introduced carbon emission responsibility factor guidance while keeping electric vehicles on rigid charging schedules. This shift directed flexible consumption toward low-carbon hours, cutting carbon emissions by 19.45 percent to 10.23 metric tons, but increased operating costs to 12,381.84 yuan and widened the peak-to-valley load difference to 877.09 kilowatts due to concentrated daytime consumption and a lack of bidirectional peak-shaving flexibility.
Scenario 3 incorporated vehicle-to-grid interaction under standard time-of-use price guidance without the carbon factor, enabling vehicles to charge during low-price periods and discharge during evening peaks. This reduced operating costs to 11,952.83 yuan and dramatically narrowed the load peak-to-valley difference by 77.07 percent to 143.72 kilowatts, though carbon emissions decreased only slightly to 12.04 metric tons. Scenario 4 combined carbon factor guidance with bidirectional vehicle-to-grid flexibility. Under this integrated configuration, operating costs fell to 11,624.76 yuan, carbon emissions declined to 10.95 metric tons, and the peak-to-valley difference was held at 260.15 kilowatts. While Scenario 4 exhibited a larger load variation than Scenario 3 because some battery capacity shifted toward carbon mitigation, it reduced operating costs, emissions, and peak-to-valley variation by 3.87 percent, 13.78 percent, and 58.50 percent, respectively, relative to the Scenario 1 benchmark.
Tracking the carbon responsibility factor before and after re-dispatch confirmed that environmental guidance altered the system’s operational intensity. Across Scenarios 2 and 4, the mean system carbon factor dropped from a pre-dispatch level of 0.8211 kilograms of carbon dioxide per kilowatt-hour down to 0.5452 kilograms in Scenario 2 and 0.5845 kilograms in Scenario 4, representing reductions of 33.6 percent and 28.8 percent, respectively, with the sharpest declines occurring during peak carbon hours. To verify these findings against the random arrival, departure, and charging states of private transportation, the research team conducted 50 independent Monte Carlo trials. Across all 50 stochastic trials, the integrated Scenario 4 configuration consistently demonstrated paired improvements over the benchmark, achieving mean reductions of 4.18 percent in operating costs, 13.09 percent in carbon emissions, and 32.06 percent in load variance, with 95 percent confidence intervals excluding zero.
The study notes specific structural boundaries in the current dispatch formulation that present opportunities for future research. While the framework utilizes the carbon factor calculated during pre-dispatch as a static reference for re-dispatch optimization, it does not implement continuous, dynamic recalculation of carbon signals in response to intra-hour operational adjustments. Furthermore, the dispatch equations operate at an aggregated system level without explicitly modeling transmission network topology, power flow physics, or localized bus voltage constraints. The investigators concluded that incorporating real-time dynamic carbon factor updates and detailed electrical network constraints will be essential steps for extending the coordinated source–grid–load–storage framework toward physical grid deployment.
Subject of Research: Low-carbon coordinated dispatch of a source–grid–load–storage power system using carbon emission responsibility factors and vehicle-to-grid flexibility
Article Title: Low-carbon coordinated dispatch of a source–grid–load–storage system considering a carbon emission responsibility factor and vehicle-to-grid interaction
Article References: Ba, T., Zeng, H., Wu, W., Jiao, D., & Huang, Y. (2026). Low-carbon coordinated dispatch of a source–grid–load–storage system considering a carbon emission responsibility factor and vehicle-to-grid interaction. Journal of Engineering and Applied Science, 73(1), Article 427. https://doi.org/10.1186/s44147-026-01253-7
Image Credits: AI Generated
DOI: 10.1186/s44147-026-01253-7
Keywords: coordinated dispatch, source-grid-load-storage, carbon emission responsibility factor, vehicle-to-grid, electric vehicles, energy storage systems, photovoltaic generation, biomass power, micro gas turbine, two-stage optimization, carbon emission trading, green certificate trading, CCER, time-of-use pricing, demand response, fuzzy chance-constrained programming, Monte Carlo simulation, load profile smoothing
News Source: Denise Maddox. (November 21, 2026). Dual Dispatch Framework Cuts Power System Emissions and Operating Costs. Scienmag.